Size: 10 AWG
Cross Section Area (mm2): 5.26
PVC Insulation Thickness (Conductor): 0.510 mm / 0.020 inches
Nylon Jacket Thickness: 0.100 mm / 0.004 inches
Outside Diameter: 4.07 mm / 0.160 inches
Allowable Ampacity: 30 Amps at 60 degrees C, 30 amps at 75 degrees C and 30 amps at 90 degrees C
Type THHN/THWN-2 building wire is intended for general purpose applications as defined by the National Electrical Code (NEC). Type THHN-THWN-2 is permitted for new construction or rewiring for 600-volt applications. Applications requiring Type THHN or THWN-2, the conductor is appropriate for use in wet or dry locations at temperatures not to exceed 90°C or not to exceed 75°C in oil or coolants. Applications requiring Type MTW conductor is appropriate for use in dry locations at 90°C, or not to exceed 60°C in wet locations or where exposed to oils or coolants. Applications requiring Type AWM conductor is appropriate for use at temperatures to not exceed 105°C in dry locations.